Float Level Transmitters

Product Overview

The UQD float ball level transmitter consists of a magnetic float, measuring guide tube, sensing element, circuit unit, junction box housing, and mounting components.

The float moves in sync with the liquid level. Through magnetic coupling, the resistance inside the sensor changes linearly. The converter then transforms this resistance change into a current signal, amplifying it into a standard 4–20 mA two-wire output, enabling remote monitoring and control of the measured liquid level.

The UQD float level transmitter is suitable for water treatment in industries such as petroleum refining, chemical processing, papermaking, food, and pharmaceuticals. It is also used for measuring liquid levels in various high-level and low-level containers in industrial production, especially suitable for underground tank level measurement.

Technical Parameters

  1. Measuring Range:
    • Rod type: H ≤ 6000 mm
    • Cable type: H ≤ 20000 mm
      (Installation space must be confirmed on site)
  2. Accuracy: ±5 mm, ±10 mm, ±20 mm
  3. Power Supply: DC 16–36V (recommended DC 24V)
    Output: DC 4–20 mA two-wire (RS485 Modbus protocol / HART protocol optional)
  4. Output Load: ≤ 500 Ω
  5. Junction Box Protection: IP65
  6. Medium Temperature:
    • Normal: -20 to 80°C
    • High temperature: ≤150°C
  7. Medium Pressure: ≤1.0 MPa
    (Standard orders typically do not exceed 2.5 MPa)
  8. Medium Conditions:
    • Viscosity ≤ 0.07 Pa·s
    • Float Φ52: density ≥ 0.8 g/cm³
    • Float Φ90 / Φ75: density ≥ 0.68 g/cm³
    • Suitable for various liquids meeting these conditions
  9. Explosion-proof Rating: Ex db II C T6 Gb
    Certificate No.: ZJEx24.1267X
  10. Standard Float Material: 304 stainless steel
  • Sizes: Φ75 (guide rod Φ20), Φ45, Φ52 (guide rod Φ20)
    Note: For lengths over 5000 mm, a cable type is recommended
Product CodeSeparatorModel CodeOutput TypeDisplay TypeGuide Tube MaterialProbe TypePressure RatingOperating TemperatureInstallation MethodMeasuring RangeSeparatorMedium DensityDescription
UQDFloat Level Transmitter
No display
91Model Code
C4~20mA
D4~20mA+HART
2No display
3LCD
4LED
1304(304L)
2316(316L)
3Stainless steel lined PTFE
4Others
GRod type
LCable type
1Atmospheric
21.0MPa
31.6MPa
42.5MPa
5Others
1Normal
2120℃
3150℃
1Flange
2Threaded
3Bracket
4Others
XXXXXXXX (mm, specify actual value)
/No definition
XXXXXXXX (kg/m³, specify actual value)
UQD91C21G1111000/1000Complete selection